Solis 6kw ip66 Hybrid Solar Inverter with 9600W Solar Capacity Dual output

Save 2%

Price:
Rs.320,000 Rs.325,000

Description

Features:

  • Generator connectivity with multiple input methods and automatic generator On/Off control
  • Automatic UPS switching 10 second 200% surge power backup overload capability
  • Supports 1ph and 3ph flexible connection with max 36kW in parallel
  • Up to 135A max charge/discharge current 6 customizable charge/discharge time settings
  • Compatible with lead-acid and lithium batteries, with multiple battery protection features
  • Supports peak shaving control in both "self-use" and "generator" mode

Download PDF

Specifications:

Input DC (PV side)
Recommended max. PV power 9.6 kW
Max. input voltage 600 V
Rated voltage 330 V
Start-up voltage 90 V
MPPT voltage range 90-520 V
Max. input current 16 A / 16 A
Max. short circuit current 24 A / 24 A
MPPT number/Max. input strings number 2/2
Battery
Battery type Li-ion / Lead-acid
Battery voltage range 40-60 V
Max. charge / discharge power 6 kW
Max. charge / discharge current 135 A
Communication CAN/RS485
Output AC (Grid side)
Rated output power 6 kW
Max. apparent output power 6.6 kVA
Operation phase 1/N/PE
Rated grid voltage 220 V / 230 V
Rated grid frequency 50 Hz
Rated grid output current 27.3 A / 26.1 A
Max. output current 30 A
Power factor >0.99 (0.8 leading - 0.8 lagging)
THDi <2%
Input AC (Grid side)
Input voltage range 187-253 V
Max. input current 40 A
Frequency range 45-55 Hz / 55-65 Hz
Output AC (Back-up)
Rated output power 6 kW
Max. apparent output power 2 times of rated power, 10 s
Back-up switch time <4 ms
Rated output voltage 1/N/PE, 220 V / 230 V
Rated frequency 50 Hz
Rated output current 27.3 A / 26.1 A
Max. output current 30 A
Max. AC Passthrough current 40 A
THDv (@linear load) <2%
Efficiency
Max. efficiency > 96.9%
EU efficiency > 96.5%
Protection
DC reverse-polarity protection Yes
Ground fault monitoring Yes
Integrated AFCI (DC arc-fault circuit protection) Yes (1)
Protection class/Over voltage category I/II (PV and BAT), III (MAINS and BACKUP and GEN)
General Data
Dimensions (W*H*D) 406*560*205 mm
Weight 24 kg
Topology High frequency isolation (for battery)
Operating ambient temperature range -40 ~ +60°C
Ingress protection IP66
Cooling concept Natural convection
Max. operation altitude 4000 m
Grid connection standard NRS 097-2-1, IEC 62116, IEC 61727, IEC 60068, IEC 61683, EN 50530, MEA, PEA
Safety/EMC standard IEC/EN 62109-1/-2, EN 61000-6-2/-3
Features
DC connection MC4 plug (PV port) / Terminal Block (BAT port)
AC connection Terminal Block
Display LED + APP
Communication RS485, CAN, Optional: Wi-Fi, GPRS, LAN
(1) Activation required.